Brief information:
The SURB-01 radiometric non-contact level level switch is designed for continuous non-contact positional level control of various media: solutions, suspensions, pulps and bulk materials filling technological equipment in tanks: tanks, trays, bunkers, etc. As well as continuous non-contact positional level control of the two media with different density.
Brief information:
The SURB-01 radiometric non-contact level level switch is designed for continuous non-contact positional level control of various media: solutions, suspensions, pulps and bulk materials filling technological equipment in tanks: tanks, trays, bunkers, etc. As well as continuous non-contact positional level control of the two media with different density.
The principle of operation of the level switch is based on measuring the density of the gamma radiation flux and activating the output signal while decreasing the density of the gamma radiation flux when it is blocked by a controlled environment. It is used for automatic control and process control in various industries.
The signaling device is a stationary device consisting of the following main components:
• The detection unit BDPS-03M • Measurement unit UAK-11.The average service life of the device is at least 10 years. The criterion of the limiting state is the economic expediency of restoring the instrument's reliability by repair.
Features:
• Microprocessor control; • Detection unit based on a plastic scintillator; • Ability to integrate into process control systems; • Two-wire line connecting the detection unit; • Diagnostics of the detection unit and the communication cable with the detection unit; • Galvanic isolation of the detection unit and the output signal from the common wire of the measurement unit; • Archiving of all events: turning the device on and off, switching the count rate through the set thresholds, failure of the detection unit, cable break; • Protection of the detection unit from erroneous connection;Detection unit BDPS-03M | |
---|---|
Options | Values |
Type of detection unit | Scintillation |
Detector material | Plastic scintillator |
Detector body material | Stainless steel |
Connection to the measuring unit | Two wire line |
Isotope sensitivity 137Cs (distance 0.5 m from the detector) | 2 (pulse / s) / kBq |
Maximum counting speed | 100000 pulse/s |
Temperature | - 30 … + 50°С |
Relative humidity | up to (95 ± 3) % |
Resistance to sinusoidal vibration | + |
Mechanical shock resistance | + |
Degree of protection | IP65 |
Overall dimensions, mm, (length * diameter) | 350 * 75 |
Weight | no more than 3,5 kg |
Measurement unit UAK-11 | |
---|---|
Options | Values |
Type of control device | Microcontroller |
Block body material | High impact plastic |
Operating modes | Positive / Negative |
Low threshold setting range | from 0 to 64999 pulse / s |
Upper Threshold Setting Range | from 0 to 64999 pulse / s |
Output Delay | Adjustable from 0 to 60 s |
Output Turn Off Delay | Adjustable from 0 to 60 s |
Discrete output for controlling an external relay | 12V DC |
Maximum Output Load | 0,5 А |
Galvanic isolation of the output signal from the common wire | + |
Detector unit supply voltage | 24V DC |
Galvanic isolation of the power supply of the detection unit from the common wire | + |
Information Display | LCD display 4 lines of 20 characters |
Diagnostics of the failure of the detection unit | + |
Diagnostics of a broken cable for communication with the detection unit | + |
Real time timer | + |
Event archiving in non-volatile memory | + |
Top Level Communication Interface | RS-485, Isolated |
Service Communication Interface | USB |
Terms of Use | |
---|---|
Air temperature for the measuring unit, °С | from 5 to +50 |
Ambient temperature for the measuring unit, °С | from -30 to +50 |
Relative humidity for the measuring unit at a temperature of + 35 ° С,% | up to (80+/-3) |
Relative humidity for the detection unit at a temperature of + 35 ° C,% | up to (95+/-3) |
Atmospheric pressure, kPa% | from 70 to 106 |